Conversion coefficients values for the Setpoint Adjustment Dial on a 7200 UC

Issue

Conversion coefficients values for the Setpoint Adjustment Dial on a 7200 UC

Product Line

TAC I/NET

Environment

I/NET site

Cause

Need for conversion coefficients values for the Setpoint Adjustment Dial on a 7200 UC

Resolution

M = 0.01666; B = -2.1333. The resolution counts range is 68 to 188.