Issue
"Couldn't parse: Illegal type:1 cannot be enum" Java error when opening a values page in an Xenta Server
Environment
Xenta 511
Xenta 527
Xenta 555
Xenta 913
Xenta 711
Xenta 731
Cause
Underscores ( _ ) are not permitted characters in the enumeration names within the Xbuilder project.
Resolution
Remove the _ (underscores) from the enumeration names and redownload the project.