Only the first 2 rows of the Specific Data\Value column are saved in the Modbus device editor.

Issue

Only the first 2 rows of the Specific Data\Value column are saved in the Modbus device editor. It is however possible to edit all the cells in the value column.

Product Line

TAC Vista

Environment

Xenta server with Modbus interface; device editor.

Cause

This is by design -  these cells were not intended to be used.

Resolution

Only enter information in the cells adjacent to the Name and Description cells.