What Schneider Electric actuator can be used to replace a 230 volt Satchwell mains actuator fitted onto a MZxxx valve?

Issue

Replacing a 230 volt Satchwell mains actuator.

Product Line

Field Devices

Environment

Satchwell

MZxxx

Valve

Mains

Actuator

Cause

Old Satchwell actuator is obsolete.

Resolution

The replacement mains actuator will be the MV15B-230 spec - 880-0460-000 for datasheet please click HERE.

To fit the MV15B-230 actuator to a Satchwell MZxxx valve a L7SV linkage is required. spec 880-0126-000