Access events not being reported for one controller.

Issue

All controllers are reporting access events except one.

Product Line

Andover Continuum

Environment

  • SystemStatus
  • Access Events

Cause

The InfinitySystemVariable SystemStatus was set to No Database.

Resolution

Once SystemStatus was set to equal Normal access events began to be reported from the controller.