UTC Setting in Controller keeps returning to 0 after being after committing changes to Controller Configuration.


Once the controllers UTC setting is set and and commited in the Controller Configuration webpage, when they are rechecked they have returned to the default setting of 0. 

Product Line

Andover Continuum


  • CX99xx
  • CX9680
  • ACX57xx
  • BCX9640
  • BCX9680
  • CX9702


This is a known issue.


Since the controllers UTC setting cannot be set properly from the controller web page, it must be set from a Plain English program in the controller. 

See Lessons Learned Article 8068