BACnet Dent PS3 PowerScout Meters Issue.

Issue

When trying to discover via BACnet they broadcast the same instance ID. Need Dent Viewpoint software and RS485 converter to change the Instance ID prior to doing Find New BACnet Devices.

Product Line

Andover Continuum, SmartStruxure Solution

Environment

BACnet MSTP

Cause

Documentation

Resolution

Use Dent Viewpoint software and RS485 converter to change the Instance ID prior to doing Find New BACnet Devices.