Time stamps of I/NET transactions are off in the Vista event and transaction windows.

Issue

Time stamps of I/NET transactions are off in the Vista event and transaction windows.

Product Line

TAC I/NET, TAC Vista

Environment

  • Xenta 527
  • I/NET Events
  • TAC Vista Workstation

Cause

Even though the SCU time stamps the transaction, the 527 will shift it according to it's time zone and date settings.

Resolution

Make sure the time is set correctly in the Xenta 527.