Issue
When logging into a Niagara R2 Enterprise Server station, the default web page displays the following error:
ERROR: Invalid template: db/Bacnet522/BACnetTemp/Josh_Plant/JoshIndex. The file does not exist on the server.
Environment
Niagara R2 Enterprise Server
Cause
There must be a background HTML page specified in the WebUIservice default template URL field in order for the web pages to display correctly.
Resolution
- Right click the WebUIservice > Properties > Config tab
- The default template that comes with a new station is /tridium/services/defaultTemplate.html
- Verify that this is correct
- For further information, refer to the Niagara Web Solutions Guide.