Issue
A system with NIC852 keys has difficulty getting the Loytec Ports to come online after an upgrade to Vista 5.0.3.
Environment
- Vista 5.0.3
- NIC852 Loytec Ports
- Orion Stack
Cause
There was a product enhancement with 5.0.3 that Loytec PCI-709 network interfaces were replaced by NIC709-PCI100 (Vista Orion stack)
Resolution
Upgrade the LCONFIG software to the newest 3.0.1 version. This software is available from http://www.loytec.com.