Issue
The current manager ID does not correspond to a known manager. This is an internal error and should be reported to customer support.
Environment
- LNS
- LonMaker
- Vista
- NL220
Cause
Power failure on the computer while adding controllers to an existing drawing. Could not open the drawing after this.
Resolution
- Restore the most recent backup where this controller did not exist.
- Open the drawing with network unattached
- Then go network attached
- Then go onnet.
- Launch System Plug-in to delete and create new group bindings. Save the file.
- Open drawing again
- Register the System Plug-in