Issue
After transferring an LNS database from NL220 or LonMaker into TAC Vista Workstation, all controllers are green (online) in Workstation. However, clicking on some programmable controllers results in an error message that states: "The blueprint is corrupted."
Environment
- TAC Vista Workstation
- Xenta programmable controllers
- Xenta 280, 281, 282, 283, 300, 301, 302, 401, 401:B
Cause
The TAC Xenta group name was too long or contained spaces. (More than 20 characters)
Resolution
Change the Xenta Group name to be less than 20 characters without any spaces.