Issue
BCX not showing up on infinity side but shows up on the Bacnet side.
Environment
Continuum Cyberstation Explorer
Cause
View options in the Continuum Explorer were set to view the Continuum Bacnet device as Bacnet Only.
Resolution
- In Continuum Explorer, select the menu item View
- Select Show Continuum Bacnet Device As
- Select Infinity Controller and Bacnet Device