I/A Series G3 (Niagara) ERROR [Current Date ] [AsdNetwork_COM3] Unlicensed: /Drivers/AsdNetwork Javax.baja.license.FeatureNotLicensedException: tac_llc:tacasd

Issue

ERROR [Current Date] [AsdNetwork_COM3] Unlicensed: /Drivers/AsdNetwork

Javax.baja.license.FeatureNotLicensedException: tac_llc:tacasd

Product Line

TAC I/A Series

Environment

I/A Series G3 (Niagara)

Asd Driver

Cause

The issue is caused by a missing certificate. Each license installed needs to have a matching certificate.

Resolution

  1. Obtain TAC_LLC Certificate
  2. Install under License Manager
  3. Reboot ENC

If issue persists verify the license file name is correct, i.e. TAC_LLC.license.   If it doesn't match this name exactly obtain new license file.