Controller with Veederoot Xdriver is resetting.

Issue

  • I connected the new cable and the netcontroller immediately reset and lost memory.
  • I reloaded the Netcontroller and before it was completed it reset and lost memory.

Product Line

Andover Continuum

Environment

  • NC9680
  • LA1
  • Xdriver
  • Veederoot

Cause

  • Improper Veederoot point configuration.
  • Corrupted Veederoot point objects.

Resolution

  • Deleted all of the Veeder-Root points.
  • Manually entered the points one at a time.