Issue
Created new bCX and can't see any of the system objects like system variables
Environment
CyberStation
bCX4040
ACX57xx
Cause
CyberStation failed to fully create the new controller object in the database.
Resolution
Delete the newly created controller from the ContinuumExplorer. Restart CyberStation. Create the controller again.