Issue
After a loss of memory and subsequent send to controller the values do not reset to their previous value.
Environment
- Cyberstation 1.9X
- NetController II
Cause
The Numeric value when controlled by a program will not save the last value to the database.
Resolution
- Edit the Numeric and set the value.
- In order for the value to persist, the setpoint flag must be set to true.
- Perform a backup to flash.