7798B replacement with 7798C

Issue

7798B replacement with 7798C

Product Line

TAC I/NET

Environment

I/NET

Cause

The .sav file for the 7798B and the 7798C are identical. 

Resolution

  1. Perform a station save on the 7798B
  2. Remove the 7798B and replace with a 7798C
  3. Save the 7798C in Netcon
  4. Select Edit>Host Computer Software
  5. Download the Software to the 7798C
  6. Connect to the controller
  7. Perform a station restore