Issue
7798B replacement with 7798C
Environment
I/NET
Cause
The .sav file for the 7798B and the 7798C are identical.
Resolution
- Perform a station save on the 7798B
- Remove the 7798B and replace with a 7798C
- Save the 7798C in Netcon
- Select Edit>Host Computer Software
- Download the Software to the 7798C
- Connect to the controller
- Perform a station restore