Issue
Getting error unhandled exception when trying to run a report of extended log data
Product Line
Andover Continuum
Environment
CyberStation
Cause
ACCTrace reveal workstation is handling excessive extended log data (>100,000 lines in ACCTrace in a couple minute)
Resolution
In the CyberStation properties, set the 'Download extended log data from Controllers on the LAN' to false.
Reboot CyberStation
If reports runs ok now the Extended logging configuration should be revised.
See Extended Logging gaps, performance and load balancing for more information.