Issue
Trying to talk to Trane Controller (MP580) and will not update. (LON)
Environment
G3/R2 Niagara
Cause
Run Frequency is a property that defines how often the program executes. If set to 0 values will not update in LON shadow object.
Resolution
Run frequency to a value other than 0.