Issue
Cannot open the LonTrunk folder for a particular UNC station in WPP in the Enterprise Server.
Getting error:
Environment
I/A Series (Niagara) R2
Cause
LonWorks jar mismatch between the Enterprise Server and the UNC.
Resolution
Alter the LonWorks jar in the Enterprise Server or the UNC's so they match.
It is recommended the Enterprise Server and it's subordinate UNC's be at the same software revisions.