Not able to get Service pin from LON devices connected with Loytec NIC from ES

Issue

LonPort is discovered and shows as online but no Service Pin is received

Product Line

SmartStruxure Solution

Environment

  • StruxureWare Building Operation ES 1.1
  • LConfig

Cause

Since StruxureWare Building Operation ES is running as a service, the legacy driver also has to be.

Resolution

  1. Open LConfig
  2. Click advanced
  3. Change Legacy Driver to run as service