Issue
Need to know minimal CyberStation user rights for security guards to be able to see video in a VideoLayout object launched from Pinpoint.
Environment
CyberStation
VideoLayouts (as opposed to VideoMonitor)
Cause
When trying to give security officers the right to click on a graphic object to open up a video layout. What Continuum security rights do they need to do this?
Resolution
Tested with v1.93. The minimal rights (keys in the Security editor application) to see video in a VideoLayout appears to be the following:
1. Run Graphics Editor.
2. VideoServer, View .
3. VideoLayout, View
4. VideoLayout, General Page
You need a hotspot on a menu page to open a Pinpoint graphic. That graphic has a button to open a VideoLayout.