Issue
Reloading a controller causes AccDataServices crash after controller is reset.
Creating controller that is offline does same as above.
Environment
CyberStation
Cause
ControllerStatus/InfinetStatus EventNotification configured to Email/Page on alarm but MS Outlook has not been installed on the machine.
Resolution
Edit the EventNotification and de-select the email/page on alarm in the actions tab and the recipient list.
OR
Install MS Outlook