Issue
Once a backup to flash is successfully performed, will the restore be successful if the acc net id changes?
Environment
bCX9640
CX9680
ACX5740
ACX5720
Cause
System design
Resolution
Upon attempting to restore a backup of its DB from flash, the controller checks its acc net id against what is in the backup, if a mismatch is found the restore operation is aborted.
The error log will error 0x000014fb in the error code column and 0x1442000c in the Data1 column.