Issue
Downloading to an SCU and a DPU 7920 Mipped board goes to 33K-38K and then fails.
Environment
All versions of I/Net software.
Cause
Possible bad memory location on the controller and or device that does not allow the device to be downloaded all the way.
Resolution
- Change the address of the sublan device
- Download the bin file and database to it
- Go to Network Configuration and verify that the doors show up and can be saved
- Verify that the device functions normally again.