Issue
How to override the valves in a TAC Xenta 101-VF
Fully open valve with TAC Xenta 101-VF
Fully close valve with TAC Xenta 101-VF
Environment
TAC Vista
TAC Xenta 101-VF
Cause
Sometimes you need to override the valves.
Resolution
In TAC Vista or Lonmaker find the SNVT nviValveOverride
HVO_OPEN opens both valves
HVO_Close closes both valves.
Don't fill in anything for flow or percent.