Object identity has been specified for an object that doesn't exist.

Issue

Trying to edit bCX from BACnet side results in the above error.

No problem from Infinity side.

Product Line

Andover Continuum

Environment

CyberStation

bCX4040

bCX4000

Cause

Configuration issue

Resolution

a) Delete bCX from BACnet side.

b) Perform find new BACnet devices from the root.

c) After device is found and present under the BACnet devices folder, right click on it and send it to the database.