Issue
A variable that is a NV-based CP and named nisse123 (for example), won't work in Xbuilder
A variable that is a NV-based NV (i.e. not a CP) and named nci123 won't work in Xbuilder
Environment
TAC Xbuilder
Cause
TAC Vista and TAC XBuilder handles SNVTs differently
Resolution
The general workaround is to ensure nci are named nci, nvi are named nvi, and nvo are named nvo.