Programmable controller does not get added. Progress window never closes

Issue

Programmable controller does not get added. Progress window never closes

Can not add programmable controller.

Product Line

SmartStruxure Solution

Environment

StruxureWare Building Operation 1.3 SP

Function block editor

TAC Xenta 301, TAC Xenta 302, TAC Xenta 401, TAC Xenta 281, TAC Xenta 282, TAC Xenta 283

Cause

Check if there are any blocks named "version". This is a reserved word that is not allowed as a name

Resolution

Open Function block editor and search your application (F7) for the word version.