Unable to save because attached device is not specified error when importing a Continuum Export file.

Issue

Getting an Unable to save because attached device is not specified error when trying to import a Cyber export file, even when using a file that has just been exported from the same Cyberstation. 

Product Line

Andover Continuum

Environment

  • Export
  • Import
  • 1.9x

Cause

Improper path specified.

Resolution

The problem was resolved by adding the target InfinityController to the path statement.