Unable to find Modbus device on RS-485 line under an Automation Server.

Issue

Unable to find Modbus device on RS-485 line under an Automation Server.

Product Line

SmartStruxure Solution

Environment

Automation Server (AS)

Modbus over serial line

Cause

Common wire is missing.

Resolution

Connect a common wire to the Shield connection on the COM port terminal