Issue
Forced inputs in Xenta 121s return to default values
Environment
- LonMaker
- NL220
Cause
Every time you hit "Apply" or "OK" in Zbuilder, the Xenta 121 will get a reset command. When the controller receives the reset command, the inputs lose their forced status and return to default values.
Resolution
After the Xenta 121 controller has been rest, the overridden points must be forced again.