Getting error when adding 2 doors on an ACX7xx controller

Issue

Getting error when adding 2 doors, Infinity controller error value does not apply to attribute

Product Line

Andover Continuum

Environment

CyberStation

CX9900

CX9680

ACX781

ACX701

Access Control

Cause

Version of the controller is 2.1x which is an Infinity version

Resolution

Chip change the controller to the correct Continuum version, 1.500012