Issue
Error message of "default port unable to find object in the DB" from InfinityProgram objects when trying to export the controller to a dump file backup by performing "Send To" --> "Text File" from workstation.
Environment
Continuum Workstation (LAN & SU)
NetController (CX99xx, CX96xx, CX97xx)
InfinetController (i2xxx , i1 controllers)
Cause
The controller was created by importing a dump file created from different system DB or by importing a dump file from a different type of controller followed by poor/incorrect modification.
Resolution
Recreate the InfinityProgram object again manually as below.
- Copy the source code of the InfinityProgram in a text file.
- Delete the InfinityProgram from Continuum.
- Create a new InfinityProgram with the same name.
- Paste the source code from the text file into the InfinityProgram editor, save the InfinityProgram.