Issue
Can not discover the proxy points for an UNC under the ObixNetwork of a Niagara G3 ENS. Nothing shows up when a Discover is performed.
Environment
Niagara G3
Cause
Obix Thread Pool count set too low in ENS
Resolution
Increase Obix Thread Pool count in the ENS ObixNetwork Property Sheet.
- Expand Drivers in the ENS
- Right-click on the ObixNetwork and select Property Sheet
- Expand the Thread Pool property
- Increase the number of threads