Unable to override an ASD point from a Niagara G3 Enterprise Server.

Issue

Unable to override an ASD point from a Niagara G3 Enterprise Server.

.

Product Line

TAC I/A Series

Environment

Niagara G3

Cause

TAC/ASD module is missing from Enterprise Server Niagara Modules folder.

Resolution

Download TAC/ASD module from The Exchange Download Center

  1. Download the matching revision module and copy the file in the Niagara Modules folder.
  2. Restart the Niagara Service and Workbench to register the module.