Issue
An existing Niagara R2 MicroSmart integration has been operational for several years. Recent changes required reprogramming of some MicroSmart controllers -- points added, points deleted, points renamed. How do these changes get uploaded to the existing station in the UNC?
Environment
Niagara R2 MicroSmart integrations (all versions)
Cause
Changes to building HVAC equipment.
Resolution
The MicroSmart driver uses the point list loaded in the PointListManager of the IbsMsService for reference. So any changes to a point type, order, id, engineering unit, or status id must be uploaded in a "new" point list.